| K | Chromel–Alumel (NiCr–NiAl) | −200 to 1,260°C | General-purpose furnaces, heat treatment, kilns, engines, and process piping | Broad operating range and widely used. At high temperatures, drift and oxidation can affect long-term accuracy. | Type K-compatible input, cold-junction compensation (CJC), and extension wire matched to Type K. |
| J | Iron–Constantan (Fe–CuNi) | −210 to 1,200°C | Legacy industrial equipment, plastics processing, and moderate-temperature furnaces | Iron leg can oxidize, so sustained high-temperature or wet environments may shorten sensor life. | Type J linearization and CJC; verify polarity and use Type J extension or compensating cable. |
| T | Copper–Constantan (Cu–CuNi) | −250 to 400°C | Refrigeration, cryogenic systems, laboratories, and food or pharmaceutical temperature monitoring | Good choice for low-temperature measurements; the copper leg limits use at elevated temperatures. | Type T-compatible input with CJC; check that the module supports the required sub-zero range. |
| E | Chromel–Constantan (NiCr–CuNi) | −200 to 900°C | Low-temperature process monitoring, environmental chambers, and moderate-temperature equipment | Produces a relatively high thermoelectric output, which can be useful for low-level signal measurement. | Type E linearization and CJC; confirm the module’s measurement range and input resolution. |
| N | Nicrosil–Nisil (NiCrSi–NiSi) | −200 to 1,300°C | High-temperature furnaces, kilns, and applications needing stable performance over time | Designed for improved stability compared with Type K in many high-temperature applications; compatibility with existing wiring must be checked. | Type N-specific input linearization and CJC; do not substitute Type K extension wire. |
| R | Platinum–13% Rhodium / Platinum (Pt–13%Rh/Pt) | 0 to 1,600°C | Glass production, high-temperature furnaces, and controlled industrial heat treatment | Precious-metal sensor with low output; protect it from contamination and mechanical damage. | Type R input, suitable low-level signal resolution, CJC, and compatible compensating cable. |
| S | Platinum–10% Rhodium / Platinum (Pt–10%Rh/Pt) | 0 to 1,600°C | Laboratory and reference measurements, glass manufacture, and high-temperature process control | Offers stable high-temperature measurement when correctly installed, but is costly and vulnerable to contamination. | Type S linearization, CJC, and an input capable of accurately resolving the relatively low sensor signal. |
| B | Platinum–30% Rhodium / Platinum–6% Rhodium (Pt–30%Rh/Pt–6%Rh) | Approximately 600 to 1,700°C for practical measurement | Very high-temperature furnaces, glass tanks, and other hot industrial processes | Best suited to high temperatures; its low thermoelectric output makes it less practical at lower temperatures. | Type B-specific input and linearization, CJC, and sufficient signal resolution for the intended operating range. |
| C | Tungsten–5% Rhenium / Tungsten–26% Rhenium (W–5%Re/W–26%Re) | Approximately 0 to 2,300°C | Specialty vacuum, inert-atmosphere, or reducing-atmosphere furnaces | Not suitable for oxidizing atmospheres at high temperatures; availability and calibration support may be limited. | Confirm that the module explicitly supports Type C or the sensor’s specified calibration; standard K/J/T inputs are not interchangeable. |
| D | Tungsten–3% Rhenium / Tungsten–25% Rhenium (W–3%Re/W–25%Re) | Approximately 0 to 2,320°C | Specialty ultra-high-temperature measurement in vacuum, inert, or reducing atmospheres | Requires a controlled atmosphere at high temperatures and specialized sensor protection and handling. | Use a module with Type D-specific support or a verified custom input curve, plus compatible wiring and CJC. |