| 1 | Standards and compliance | Confirm that the proposed low-voltage assembly is designed and verified for the applicable project requirements. IEC 61439-1 covers general rules for low-voltage switchgear and controlgear assemblies; IEC 61439-2 covers power switchgear and controlgear assemblies. | Applicable standard editions, design-verification records, certificates where relevant, and confirmation that the documents cover the quoted product configuration. | 15% |
| 2 | Electrical ratings | Check rated operational voltage, rated current, frequency, number of poles, and the required distribution arrangement against the project specification. | Product datasheets, single-line diagrams, equipment schedules, and a completed technical-compliance schedule showing any deviations. | 15% |
| 3 | Short-circuit withstand capability | Verify that the assembly’s short-circuit ratings and protective-device coordination meet the available fault level and protection design at the installation point. | Short-circuit rating documentation, protection-device details, coordination information, and supporting design-verification evidence for the offered configuration. | 15% |
| 4 | Temperature-rise performance | Assess whether the assembly’s rated current, enclosure arrangement, ventilation, and operating conditions are supported by temperature-rise design verification. | Temperature-rise verification records or calculations, stated ambient conditions, and any applicable derating guidance. | 10% |
| 5 | Enclosure protection | Match the required protection against access to hazardous parts and ingress of solid objects or water to the installation environment. IEC 60529 defines the IP Code used to classify enclosure protection. | Declared IP rating, test or verification documentation, and details of the enclosure configuration to which the rating applies. | 8% |
| 6 | Busbars and electrical connections | Review busbar material, cross-section, joint design, plating where specified, support spacing, and the method used to control connection torque and contact resistance. | Bill of materials, busbar drawings, material specifications, assembly instructions, and production inspection records. | 8% |
| 7 | Internal separation and maintainability | Check the specified form of internal separation, access to functional units, cable termination space, labeling, and provisions for safe inspection and maintenance. | General-arrangement drawings, section views, separation details, maintenance instructions, and confirmation of the offered configuration. | 7% |
| 8 | Routine verification and factory testing | Confirm that each completed assembly receives the applicable routine verification and that inspection and test responsibilities are clearly defined. | Routine-verification checklist, sample test records, inspection plan, and proposed factory acceptance test procedure where required by the project. | 8% |
| 9 | Engineering and customization capability | Evaluate the supplier’s ability to adapt dimensions, incoming and outgoing arrangements, metering, protection, control wiring, and communication interfaces to the project specification. | Project-specific drawings, interface schedules, revision-control process, and documented approval workflow for design changes. | 7% |
| 10 | Delivery, documentation, and after-sales support | Assess the proposed manufacturing schedule, spare-parts availability, warranty terms, technical support arrangements, and completeness of handover documentation. | Project delivery schedule, written warranty and service terms, spare-parts list, operation and maintenance manuals, and as-built document list. | 7% |