| Bolted Busbar Connectors | Joining copper or aluminum busbars in low- and medium-voltage assemblies. | Rated current, busbar material and dimensions, joint geometry, clearance, and specified bolt torque. | Check for looseness, corrosion, discoloration, and signs of overheating. Retorque only when the equipment instructions permit it. |
| Compression Cable Lugs | Terminating stranded power cables at breaker, busbar, or equipment terminals. | Conductor material and size, lug material, barrel dimensions, applicable crimping tool and die, and terminal-hole size. | Look for damaged strands, cracks, corrosion, or an irregular crimp. Use the specified tooling and installation procedure. |
| Mechanical Shear-Bolt Connectors | Connecting conductors where a mechanical, tool-installed termination is specified. | Approved conductor sizes and materials, connector range, terminal fit, and manufacturer-specified installation method. | Inspect for movement, corrosion, or thermal damage. Do not reuse components intended for one-time installation. |
| Separable Elbow and Tee Connectors | Shielded cable connections to compatible medium-voltage bushings and interfaces. | Voltage class, interface dimensions, cable insulation diameter, conductor range, current rating, and shielding arrangement. | With equipment safely isolated, check for cracks, contamination, moisture, damaged seals, and signs of tracking. Follow the specified cleaning and assembly procedure. |
| Primary Disconnect Contacts | Removable connections between draw-out circuit breakers and stationary switchgear compartments. | Contact geometry, rated current, alignment, contact pressure, plating compatibility, and equipment-specific fit. | Inspect for wear, pitting, overheating, contamination, and misalignment. Replace contacts that exceed service limits. |
| Tulip Contacts | Spring-finger contacts used in some withdrawable switchgear primary disconnect assemblies. | Matching contact dimensions, rated current, spring force, contact material, and alignment with the mating conductor. | Check finger movement, contact wear, discoloration, and spring condition. Use only approved contact lubricant, if specified. |
| Finger-Cluster Contacts | Multiple-contact assemblies used to provide a sliding electrical connection in draw-out equipment. | Correct cluster size, contact pressure, current rating, material, and compatibility with the mating surface. | Look for broken or weak fingers, uneven wear, contamination, and overheating. Confirm the assembly moves freely as designed. |
| Spade or Palm Terminals | Flat termination points for cable lugs or flexible conductors at equipment terminals. | Hole pattern, conductor termination method, current rating, terminal material, and available space for safe clearances. | Inspect the bolted interface for corrosion, looseness, and heat damage. Keep mating surfaces clean and follow specified torque values. |
| Protective-Earth Connectors | Bonding enclosure sections, doors, cable screens, and grounding conductors to the protective-earth system. | Required fault-current duty, conductor size, bonding method, corrosion environment, and continuity requirements. | Verify secure bonds and inspect for corrosion, broken bonding straps, or paint that interrupts the intended contact path. |
| Control-Circuit Terminal Blocks | Terminating and distributing control, signaling, and measurement wiring inside switchgear panels. | Conductor size, voltage and current ratings, terminal type, circuit identification, and required separation between circuits. | Check wire security, labels, insulation, and signs of heat or corrosion. Tighten screw terminals only to the specified torque. |