| 1 | Two-Way Straight Junction | Two 200 A loadbreak interfaces arranged in a straight line. | Direct cable continuation, compact feeder extensions, and simple underground cable runs. | 15 kV class 200 A continuous Typical BIL: 95 kV | Match the cable insulation diameter, conductor size, interface type, phase spacing, and enclosure dimensions. | Use only with compatible separable connectors. Install with the circuit de-energized unless the complete assembly is specifically rated for the intended switching operation. | Inspect interfaces, insulation surfaces, grounding connections, and torque-controlled hardware during planned outages. | High for straight-through feeders |
| 2 | Two-Way Angled Junction | Two 200 A interfaces positioned at an angle to reduce cable bending stress. | Pad-mounted equipment, narrow vaults, and installations where cable routing cannot remain straight. | 15 kV class 200 A continuous Loadbreak capability per certified assembly | Check minimum cable-bending radius, elbow orientation, phase clearance, and available working space. | Prevent mechanical strain on elbows and bushings. Maintain the manufacturer-specified parking or grounding arrangement for unused interfaces. | Check for cable movement, stress at the interface, contamination, moisture ingress, and enclosure corrosion. | High for constrained layouts |
| 3 | Three-Way Junction | One incoming interface and two outgoing interfaces, or the reverse arrangement. | Feeder branching, underground network distribution, and service-area expansion. | 15 kV class 200 A continuous per interface System fault rating per design | Verify total feeder loading, branch-current coordination, phase identification, and space for elbow removal. | Every exposed interface must be properly capped, parked, or connected. Grounding and phasing must be verified before energization. | Inspect all three interfaces and branch cables; thermographically inspect loaded connections when permitted by site procedures. | High for feeder branching |
| 4 | Four-Way Junction | Four 200 A interfaces for multiple feeder directions or sectionalized circuits. | Networked distribution, multi-directional underground feeders, and compact switching points. | 15 kV class 200 A continuous per interface Fault withstand per certified design | Evaluate enclosure volume, cable congestion, load diversity, switching sequence, and fault-duty coordination. | Clearly identify each phase and circuit. Apply an approved switching plan and maintain safe approach distances during testing. | Perform periodic visual inspection, connection checks, enclosure cleaning, and condition assessment of every interface. | Medium to high for networked systems |
| 5 | Feed-Through Junction | Two aligned interfaces designed to maintain a continuous cable path through a sectionalizing point. | Temporary bypasses, cable replacement, feeder extension, and sectionalized underground circuits. | 15 kV class 200 A continuous Continuous current limited by the lowest-rated component | Confirm that the junction, connectors, cable, and protective devices have compatible voltage, current, and fault ratings. | Do not treat a feed-through assembly as a visible isolation point unless the complete system provides approved isolation and grounding facilities. | Inspect sealing, cable support, interface condition, and signs of heating at the through connection. | High for cable continuity and bypass work |
| 6 | Sectionalizing Junction | Junction equipped with separable interfaces that support planned feeder segmentation. | Fault isolation, outage minimization, looped distribution, and maintenance switching. | 15 kV class 200 A continuous Loadbreak operation only within certified limits | Coordinate with upstream and downstream protection, switching procedures, network topology, and available fault current. | Use approved voltage-detection, phasing, grounding, and switching procedures. Loadbreak operation must remain within the assembly rating. | Maintain operating labels, inspect interfaces, verify grounding points, and review switching records. | High for reliability-centered distribution |
| 7 | Junction with Parking Provision | Loadbreak junction with designated insulated parking positions for disconnected elbows. | Safe temporary storage of energized or de-energized separable connectors during switching and maintenance. | 15 kV class 200 A circuit interfaces Parking rating must be separately confirmed | Verify the parking provision is compatible with the connector, grounding method, enclosure layout, and operating procedure. | Never use an unapproved location as a parking point. Confirm whether the parked connector is insulated, grounded, or intended only for de-energized storage. | Inspect parking interfaces for contamination, tracking, cracks, damaged caps, and loss of mechanical retention. | High where frequent switching is expected |
| 8 | Grounding-Point Junction | Junction arrangement incorporating an approved grounding or test interface. | Temporary cable grounding, maintenance isolation, testing, and controlled access to underground circuits. | 15 kV class 200 A current path Grounding duty per certified accessory and procedure | Confirm ground connection rating, fault-current duration, cable shield compatibility, and the required sequence of operation. | Ground only after absence of voltage is established. Use properly rated grounding equipment and follow the site lockout/tagout procedure. | Inspect ground contacts, mechanical locking parts, bonding conductors, and corrosion protection. | High for maintenance and safety programs |
| 9 | Compact Vault Junction | Space-optimized multi-interface assembly intended for underground vaults or confined equipment compartments. | Urban distribution, vault installations, compact pad-mounted equipment, and retrofit projects. | 15 kV class 200 A continuous per interface Thermal performance depends on enclosure and installation | Assess heat dissipation, flooding risk, cable bend radius, working clearance, drainage, and lifting access. | Provide adequate working space and water-control measures. Do not obstruct pressure-relief or ventilation features where specified. | Inspect after flooding, check enclosure seals, remove debris, and verify that cable supports have not shifted. | Medium to high for space-limited sites |
| 10 | Outdoor Enclosed Junction | Loadbreak interfaces housed in a weather-resistant enclosure for above-ground installation. | Pad-mounted distribution, outdoor feeder transitions, construction power, and exposed switching locations. | 15 kV class 200 A continuous Enclosure rating selected for the environment | Consider ultraviolet exposure, rain, ice, salt, wildlife, vandalism, enclosure ingress protection, and operating temperature. | Keep doors, barriers, warning labels, and interlocks functional. Maintain required clearances and prevent unauthorized access. | Inspect enclosure hardware, seals, labels, corrosion, cable entries, and evidence of tracking or wildlife intrusion. | High for exposed outdoor installations |