| Meaning of RCCB | Residual Current Circuit Breaker. It detects an imbalance between the current flowing through the live conductor(s) and the current returning through the neutral conductor. | An RCCB is designed to disconnect a circuit when residual current is detected. It does not, by itself, provide overload or short-circuit protection. |
| How it trips | In normal operation, outgoing and returning currents balance. If some current leaks to earth—potentially through a person—the imbalance operates the sensing mechanism and opens the contacts. | Tripping can reduce the duration of electric shock exposure, but an RCCB does not make contact with live parts safe or prevent every shock. |
| Overcurrent protection | A separate fuse or circuit breaker is normally required for overload and short-circuit protection. An RCBO combines residual-current and overcurrent protection in one device. | Check that the installation has the required overcurrent protection and that the RCCB is coordinated with it. |
| Type AC | Designed to detect sinusoidal alternating residual current. | Use only where permitted by local rules and where the connected loads are known to produce compatible residual-current waveforms. It may not be suitable for equipment that can produce pulsating DC or other waveform components. |
| Type A | Detects sinusoidal AC and pulsating DC residual current. | A common choice for many general-purpose circuits with electronic loads, but it is not suitable for every appliance or installation. |
| Type F | Designed for specified mixed-frequency residual currents, including certain single-phase variable-speed equipment; it also covers Type A detection characteristics. | Consider it where equipment instructions or the circuit design call for protection suited to single-phase frequency-controlled loads. |
| Type B | Designed to detect AC, pulsating DC, and smooth DC residual currents within the device’s specified operating range. | May be required for some three-phase drives, inverters, EV charging arrangements, or other equipment capable of producing smooth DC residual current. Follow equipment instructions and local standards. |
| 30 mA residual-current rating | A common sensitivity for additional protection against electric shock in many applications. The exact requirement depends on local electrical rules and the circuit. | Do not treat 30 mA as a guarantee against injury. Correct installation, earthing, equipment condition, and timely testing remain essential. |
| Higher ratings, such as 100 mA or 300 mA | May be used for particular fire-protection or upstream coordination purposes, depending on the installation and applicable rules. | These ratings are not a general substitute for 30 mA additional protection where that protection is required. |
| Which type is best in 2026? | There is no universally best type. The appropriate choice depends on the load’s possible residual-current waveform, device instructions, installation design, and local regulations. | Type A is often a practical starting point for ordinary modern circuits; choose Type F or Type B when the connected equipment or applicable rules require their additional detection capability. Have a qualified electrician verify the selection. |
| Testing and maintenance | Many RCCBs include a test button that checks the device’s operating mechanism under the conditions specified by its manufacturer. | Test at the interval stated by the manufacturer and local rules. A test-button check does not replace professional inspection or instrument testing. |