| Purpose of the test | Checks whether the insulation around conductors, terminals, and connected circuit parts prevents unwanted leakage current. | A high-voltage direct-current test is applied for a controlled period and the resulting resistance is measured in megohms (MΩ). | The test evaluates insulation condition; it does not replace an MCB trip-current or trip-time test. |
| Test instrument | An insulation resistance tester, commonly called an insulation tester or megohmmeter, generates a regulated DC test voltage and displays insulation resistance. | Common selectable outputs include 250 V DC, 500 V DC, and 1,000 V DC. | The selected voltage must match the circuit rating, applicable rules, and the requirements of connected equipment. |
| MCB status before testing | The MCB and the circuit under test must be isolated from the supply before any insulation measurement is made. | Supply disconnected; MCB switched off or isolated as required by the test arrangement. | Never perform an insulation resistance test on an energized circuit. |
| Initial safety checks | Verify isolation, prevent reconnection, confirm the absence of voltage, and inspect the MCB, wiring, terminals, and enclosure for visible damage. | Use an approved voltage detector and follow the applicable lockout and verification procedure. | Only a suitably trained and authorized person should carry out the test. |
| Sensitive equipment | Disconnect or protect electronic controls, surge-protection devices, dimmers, power supplies, and other equipment that may be affected by the DC test voltage. | Use the equipment manufacturer’s instructions; 250 V DC may be appropriate for some sensitive circuits when permitted. | Applying an insulation test to connected electronics can cause damage or produce misleading results. |
| Typical test voltage | The test voltage is selected according to the nominal circuit voltage and the governing installation standard. | For many low-voltage circuits up to 500 V, 500 V DC is commonly used. Lower-voltage circuits may require 250 V DC. | Do not select a higher voltage simply to obtain a more impressive reading. |
| Line-to-neutral test | Checks insulation between the line conductor and the neutral conductor. | Connect one tester lead to line and the other to neutral, with the circuit isolated and suitable equipment disconnected. | A low value may indicate damaged insulation, moisture, contamination, or an item still connected to the circuit. |
| Line-to-earth test | Checks insulation between the line conductor and the protective earth or exposed-conductive-parts bonding system. | Connect one tester lead to line and the other to protective earth. | This test helps identify leakage paths from energized conductors to accessible metalwork. |
| Neutral-to-earth test | Checks insulation between neutral and protective earth downstream of the intended supply arrangement. | Connect one tester lead to neutral and the other to protective earth. | Unexpectedly low resistance can indicate a neutral-to-earth connection, wiring fault, or connected equipment leakage. |
| Test duration | The tester applies DC voltage while the reading stabilizes or for the duration required by the applicable procedure. | A 60-second measurement is commonly used for formal insulation resistance testing. | Follow the relevant electrical code, inspection procedure, or maintenance specification. |
| Common acceptance reference | Many low-voltage installation requirements use a minimum insulation resistance value for ordinary circuits. | 1 MΩ is a commonly used minimum reference for circuits up to 500 V, subject to local requirements and circuit type. | The applicable standard and equipment instructions take priority over this general reference. |
| Example result: line-neutral | Illustrative result from a dry, disconnected low-voltage circuit. | 500 V DC applied; measured resistance: 86 MΩ. | Above the 1 MΩ reference; record as a satisfactory example result when permitted by the applicable standard. |
| Example result: line-earth | Illustrative result from the same type of isolated circuit. | 500 V DC applied; measured resistance: 74 MΩ. | Above the 1 MΩ reference; compare with previous maintenance results for deterioration trends. |
| Example result: neutral-earth | Illustrative result from a circuit with no unintended downstream neutral-earth connection. | 500 V DC applied; measured resistance: 92 MΩ. | High resistance is generally expected after suitable equipment has been disconnected. |
| Low or unstable reading | A low, falling, or unstable value may result from moisture, contamination, damaged cable insulation, incorrect connections, or connected loads. | For example, a reading below 1 MΩ requires investigation where the 1 MΩ reference applies. | Separate the circuit into sections and retest to locate the affected part. Do not energize until the cause is assessed. |
| Discharge after testing | Tested conductors can retain a charge because of cable capacitance or connected components. | Allow the tester to discharge the circuit, or discharge it using the approved procedure before touching conductors. | Confirm the circuit is safe before removing leads or restoring connections. |
| Final documentation | Record the circuit identification, test voltage, test connections, measured resistance, date, and tester details. | Example record: “Circuit A; 500 V DC; L-N 86 MΩ; L-E 74 MΩ; N-E 92 MΩ; 60 s.” | Restore disconnected equipment, close the enclosure, remove safety controls only when authorized, and verify normal operation. |