| Rooftop PV system in an area with frequent thunderstorms, with an external lightning protection system | Partial lightning current may enter the PV wiring or electrical system; nearby strikes can also induce surges. | Consider a Type 1+2 PV DC SPD at the array or building entry, coordinated with the lightning protection and bonding design. Protect the AC side as required by the electrical installation design. | Confirm the SPD is intended for PV DC use and complies with IEC 61643-31 or the applicable local standard. Check the required impulse current rating (Iimp) against the lightning protection design; do not select it from a generic value alone. |
| Rooftop PV system without an external lightning protection system, but with nearby lightning exposure | Induced surges from nearby lightning and switching events can reach the inverter through DC and AC conductors. | A Type 2 PV DC SPD is commonly considered on the DC side, with coordinated AC-side surge protection where required. | Check the Type 2 nominal discharge current (In) and maximum discharge current (Imax), as well as the protection level (Up). Ratings must suit the system design and applicable standards. |
| PV array and inverter separated by a long DC cable run | Long conductors can pick up induced surges; cable length can also reduce the effective protection at the equipment. | Assess protection at both the array end and inverter end. If the cable route is long, an additional coordinated SPD near the inverter may be appropriate. | IEC-based guidance commonly calls for additional protection when the distance between an SPD and the equipment to be protected exceeds about 10 m. Confirm the applicable local rules and the manufacturer’s installation instructions. |
| Ground-mounted array with long outdoor DC cable routes | Long exposed wiring increases the opportunity for induced surges and potential differences between the array and building. | Use a coordinated protection plan for the array, cable entry, and inverter; assess bonding and earthing together with SPD placement. | Keep SPD connecting leads short and direct, follow the required conductor routing, and ensure all connected SPDs are suitable for the PV circuit voltage and earthing arrangement. |
| Any PV system with a high maximum string voltage | An SPD with an insufficient continuous operating voltage may conduct during normal operation or fail prematurely. | Select a PV DC SPD with a maximum continuous operating voltage (Ucpv) suitable for the system’s maximum cold-weather open-circuit voltage. | Calculate the maximum array Voc using the module data and the lowest expected site temperature. Ucpv must not be lower than the resulting maximum PV voltage; follow the SPD and system documentation. |
| Inverter or other sensitive equipment with a specified impulse withstand voltage | Residual surge voltage reaching the equipment may exceed its insulation withstand capability. | Choose an SPD with a protection level (Up) coordinated with the equipment’s impulse withstand rating; consider lead length and coordination with upstream or downstream SPDs. | Check the equipment documentation and ensure the effective protection voltage at the equipment is suitable. A lower stated Up alone does not replace correct installation and coordination. |
| PV system connected to a building’s AC distribution system | Surges can arrive through the utility supply or be transferred between the AC and PV circuits. | Assess AC-side SPD protection separately from PV DC protection. Type 1, Type 2, or combined protection depends on the building’s lightning protection and installation design. | For AC SPDs, verify suitability for the supply system, voltage, earthing arrangement, and applicable standard, such as IEC 61643-11. Coordinate the AC and DC protection devices. |
| System exposed to lightning risk but with no documented site assessment | Protection needs may be underestimated if local lightning exposure, building layout, cable routes, or existing lightning protection are unknown. | Complete a site-specific risk assessment before choosing SPD type and ratings; use qualified electrical and lightning protection professionals where required. | Consider local codes, lightning protection measures, array location, cable routing, earthing and bonding, and the equipment’s withstand ratings. No single SPD rating is appropriate for every installation. |