| Product Type | Cap-and-pin suspension insulator | Designed for overhead transmission and distribution lines |
| Applicable Standard | IEC 60305; commonly used with IEC 60120 coupling requirements | Confirm the required national standard, routine tests, and acceptance criteria before purchase |
| Nominal Electromechanical Failing Load | 40 kN | The “40” designation in U40B refers to the nominal mechanical rating in kilonewtons |
| Insulator Class | U40B suspension unit | Suitable for assembly into strings with the required voltage and pollution-performance level |
| Insulating Material | Toughened soda-lime-silica electrical glass | Glass provides visible damage indication and stable dielectric performance when properly processed |
| Metal Hardware | Hot-dip galvanized forged steel cap and pin | Galvanizing protects steel hardware against atmospheric corrosion; coating requirements should be specified in the purchase contract |
| Cementing Material | Portland cement or approved sulfur-free cementing compound | The cement interface should resist thermal and mechanical stresses during service |
| Nominal Diameter | Approximately 175 mm | Verify dimensional tolerances against the approved drawing |
| Nominal Unit Height / Spacing | Approximately 110 mm | Used to calculate the number of units required in a suspension string |
| Nominal Creepage Distance | Approximately 185 mm | Polluted or coastal installations may require longer-creepage alternatives or additional design measures |
| Nominal Dry Arcing Distance | Approximately 85 mm | Actual flashover performance depends on string arrangement, altitude, pollution, and weather conditions |
| Power-Frequency Withstand Voltage, Dry | Approximately 65 kV | Typical reference value for a single unit; test configuration must follow the applicable standard |
| Power-Frequency Withstand Voltage, Wet | Approximately 25 kV | Wet-test results can vary with electrode arrangement and test procedure |
| Lightning Impulse Withstand Voltage | Approximately 100 kV | Use the certified test report for project-specific insulation coordination |
| Puncture Withstand Voltage | Approximately 130 kV | Puncture testing is performed under specified laboratory conditions and should not replace system-level design verification |
| Standard Coupling | Typical 16A ball-and-socket coupling | Confirm pin diameter, socket dimensions, locking device, and interchangeability requirements |
| Approximate Unit Mass | Approximately 2.5–2.8 kg | Final weight depends on hardware configuration, cementing design, and manufacturing tolerances |
| Typical Applications | Suspension and tension strings on overhead lines | Used where the required mechanical load, insulation level, pollution class, and fitting system are compatible |
| Recommended Buyer Checks | Type-test certificate, routine-test records, dimensional drawing, glass quality, zinc-coating thickness, and packing method | Request samples or inspection records before volume production and verify compliance with the destination-country grid specification |